Self-Diagnosis and Error Codes
ORCA Level Sensors include the following diagnosis features:
- Self-Test: When triggered by the respective IO-Link System Command, the RGB LED is checked electrically.
- Monitoring of Supply and internal Voltages and MCU Temperature
- Overload Detection on digital and analog outputs
Detected errors are indicated via IO-Link Events and/or in the Error Code IO-Link Parameter, as well as by blinking patterns of the LED.
Error Codes
| Blink Code | IO-Link Error Code | Description |
|---|---|---|
| 1 | 0x0001 | Internal error |
| 2 | 0x0002 | Error with intermediate voltage |
| 4 | 0x0008 | Supply voltage overrun / underrun |
| 8 | 0x0080 | Parameter memory error |
| 9 | 0x0100 | Parameter error |
| 12 | 0x0800 | LED error |
| 13 | 0x1000 | Overload on digital output |
| – | 0x2000 | Overload on analog output |
| 15 | 0x4000 | Temperature overrun |
Revision History
Rev. A – 2024-04-16